PFD
avg
T
Proof
= 1 year
T
Proof
= 5 years
T
Proof
= 10 years
< 0. 016 x 10
-2
< 0. 081 x 10
-2
< 0. 162 x 10
-2
PFH [1/h] < 3. 7 x 10
-8
/h
Double channel architecture
Here you see an example how the measuring system in double
channel architecture can be used in an application with
demand rate SIL3. ACommon Cause Factor of beta = 10 %
(worst case) is taken into account.
If the instruments are used in another (multiple channel)
architecture, the values must be calculated for the selected
application by means of the above failure rates.
SIL3 (Safety Integrity Level)
HFT = 1 (Hardware Fault Tolerance)
Mode switch is set to "max"
PFD
avg
T
Proof
= 1 year
T
Proof
= 5 years
T
Proof
= 10 years
< 0. 007 x 10
-3
< 0. 036 x 10
-3
< 0. 073 x 10
-3
PFH [1/h] < 1. 8 x 10
-8
/h
Mode switch is set to "min"
PFD
avg
T
Proof
= 1 year
T
Proof
= 5 years
T
Proof
= 10 years
< 0. 015 x 10
-3
< 0. 076 x 10
-3
< 0. 153 x 10
-3
PFH [1/h] < 2. 0 x 10
-8
/h
SIL3 (Safety Integrity Level)
HFT = 1 (Hardware Fault Tolerance)
Mode switch is set to "max"
PFD
avg
T
Proof
= 1 year
T
Proof
= 5 years
T
Proof
= 10 years
< 0. 018 x 10
-3
< 0. 091 x 10
-3
< 0. 184 x 10
-3
PFH [1/h] < 2. 3 x 10
-8
/h
Mode switch is set to "min"
Architecture 1 oo2D - Overll
protection
Architecture 1 oo2D - Dry run
protection
Functional safety
34 OPTISWITCH 310 0 C - with two-wire output