Mode on the sensor Level Signal current - Sensor Signal lamp sensor
Fault signal
(min./max. mode)
any <2.3 mA
ashes red
OPTISWITCH 3100 C level switch with signal conditioning
instrument
1)
The following chart provides an overview of the switching
conditions depending on the adjusted mode of the signal
conditioning instrument and the level.
Note:
Keep in mind that the mode switch of OPTISWITCH 3100 C
must be always set to "max.".
Mode on the signal
conditioning instru-
ment
Level Signal current -
Sensor
Signal lamp sensor Signal lamp, sig-
nal conditioning
instrument
Mode A
Overll protection
approx. 8 mA
Green
Mode A
Overll protection
approx. 16 mA
red
Mode B
Dry run protection
approx. 16 mA
red
Mode B
Dry run protection
approx. 8 mA
Green
Fault signal
(mode A/B)
any <2.3 mA
ashes red
1)
You will nd suitable signal conditioning instruments in the Technical data
OPTISWITCH 3100 C - with two-wire output 21