Directed Electronics 3100 Instruções de Operação Página 20

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 48
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 19
min.-min.detection or dry run detection) on the signal
conditioning instrument.
When used on a control system, the following values apply:
l min. mode
- Vibrating element uncovered - 16 mA ±1 mA
- Vibrating element covered - 8 mA ±1 mA
l max. mode
- vibrating element uncovered - 8 mA ± 1 mA
- vibrating element submerged - 16 mA ± 1 mA
Control lamp for indication of the switching condition.
l green = 8 mA
l red = 16 mA
l red (ashing) = Failure (<2.3 mA)
6.3 Funct ion chart
OPTISWITCH 3100 C level sensor
The following chart provides an overview of the switching
conditions depending on the adjusted mode and level.
Mode on the sensor Level Signal current - Sensor Signal lamp sensor
max.
Overll protection
8 mA
Green
max.
Overll protection
approx. 16 mA
red
min.
Dry run protection
approx. 8 mA
Green
min.
Dry run protection
approx. 16 mA
red
Signal lamp (5)
20 OPTISWITCH 310 0 C - with two-wire output
Setup
29955-EN-060112
Vista de página 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 47 48

Comentários a estes Manuais

Sem comentários