PSS EVE0105 A-(en) VAC D300 7
Manual local settings:
Actuatormode...........linear or rotary
Linear valve ...........leftorright mounted
Rotaryactuator.........opening clockwise or
counter-clockwise
Characteristic of setpoint . . . linear, equal percentage,
invers- equal percentage
or custom (22 points)
Valvefunction ...........opens or closes with
increasing setpoint
Split range .............freeupper and lower values
Travellimits.............freeupper and lower values
Cutoffs.................freeupper and lower values
Control parameters .......Determined during Autostart.
Working range ...........freely adjustable (for
indication on LCD
Manual adjustment of......P-gain, I-time,
T63-time and dead band
Manual operation .........Manual input of setpoint to
drive the valve
Pneumatic test ...........Functiontotestthepneu-
matic output
Workshop ..............input and angle calibation
LCD language ...........dependent on version
LCD orientation ..........dependent on version
Bus address.............PROFIBUS-PA only
Simulation ..............FOUNDATION Fieldbus only
Software supported configurations:
- by means of Hand Held Terminal (HART)
- PC among others by means of PC20/ PC50 /IFDC
- I/A Series System and other DCSs
Failure handling
Safety position at
- Air supply failure ........pressurey1=zero
- Electric power failure .....pressurey1=zero
- Failure of electronics .....pressurey1=zero
- Failure of communication is recognized by configurable
watch dog with response delay of 0.1 s to 24 h
Behavior ...............configurable as
- pressure y1 = zero or
- stop at last value or
- a configured value
Diagnostic report .........viacommunication and local
LCD
Historicalstatus .........issetifalarm was activated
at any time
(also just short alarms)
Reset..................byacknowledging