18 VAC D300
ADDITIONAL EQUIPMENT
(built into basic device, version FoxCom with FM / CSA approval)
Additional Inputs / Outputs:
Two binary outputs
(limit signals) - Code P
(Options for electronics family AI 638 per FM 3003731,
CSA 1001984 and CSA 1001988)
2 galvanically separated binary outputs
Signaling of limit value violation of the measured valve
position, configurable
Two-wire system, according to DIN 19234, for external
supply.
supply voltage ...........DC8to36V
1) 2)
Logic:
limit value not exceeded ...<1mA
limit value exceeded......>2.2mA(typ.6mA)
device fault ............<50µA
Reference: AB1 for upper, AB2 for lower limit
Terminals for AB1 ........81+,82ñ
AB2.........83+,84ñ
Electrical classification hereto:
(Electronics family BIA 637)
see Certificate of Conformity. EX EVE0105 A
Type of protection FM " intrinsic safety"
(Electronics family per FM 3003731)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection FM "non-incendive"
(Electronics family per FM 3003731)
Class I, Div. 2, Groups A, B, C, D, F, G;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection CSA "intrinsic safety"
(Electronics family per CSA 1001984 and CSA 1001988)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
*) Under development
1) Other values in hazardous areas
2) On request we can specify higher voltage limits
Additional Inputs / Outputs:
Two Binary inputs - Code BI
(Options for electronics family AI 638 per FM 3003731,
CSA 1001984 and CSA 1001988)
Two independent binary inputs, supplied by basic device,
for connection of sensors.
A connected switch is loaded with 3.5 V, 150 µA.
The binary inputs can be used for diagnostics or also
configurable for the control functions:
Switch 1 Switch 2 Actuator control function
close close normal operation
open close go to stop at 0 %
close open go to stop at 100 %
open open hold last position
Terminals for EB1 ........13+,14ñ
EB2.........15+,16ñ
Electrical Classification hereto:
(Electronics family BIA 637)
see Certificate of Conformity EX EVE0105
Type of protection FM "intrinsic safety"
(Electronics family per FM 3003731)
ClassI,Div.1,GroupsA,B,C,D;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection FM "non-incendive"
(Electronics family per FM 3003731)
ClassI,Div.2,GroupsA,B,C,D,F,G;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection CSA "intrinsic safety"
(Electronics family per CSA 1001984 and CSA 1001988)
ClassI,Div.1,GroupsA,B,C,D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
PSS EVE0105 A - (en)