PSS EVE0105 E-(en) SRD991 3
OVERVIEW
The SRD991 consists of a basic device with a digital controller that supports different communication protocols
(or also simply 4-20 mA input). Into this basic device, additional equipment can be built such as plug-in cards for
electrical input/output signals, position feedback and pressure sensors.
The pneumatic part is available in different versions (single / double acting or spool valve). For very large
actuators, boosters with increased air capacity can be flanged on. Also, different manifolds for connection of gauges
can be flanged on. For the pneumatic screw connections we offer different threads in the housing and adapters.
For use in hazardous areas there are approvals according to ATEX, FM, CSA ...
The device can be configured locally by means of push buttons and LCD / LED, or with PC + EDC82 Modem
connected to the service plug of the SRD991. By means of communication the device can be configured remotely via
FDT/DTM.
A large variety of attachment kits for all common valves and actuators are available. The list “AttachmentKits.pdf” is
updated continuously and can be found on the Internet here
.
For high temperature or high vibration application, we recommend to mount the SRD991 remotely and not directly
on the valve. For this, use the potentiometer unit (like the SRI990 - TXQxxxxx - H).
Please consult TI EVE0105_R
for specifications.
To ensure the high performance of the positioner, we offer Advanced Diagnostics and Premium Diagnostics utilities:
Premium Diagnostics Advanced Diagnostics
Autostart Yes Yes
Custom Characterization Yes Yes
Autodiagnostic Yes Yes
Alarm Management Yes Yes
Alarm Output for Switching (with Optionboard) Yes Yes
Status List acc. NE107 Yes Yes
Position History Yes Yes
Response History Yes Yes
On Line Friction Yes
Stepping Signature Yes
Ramping Signature Yes
Sensitivity Signature Yes
Valve Signature Yes
PST (Partial Stroke Test) Yes
PST Predictive Maintenance Yes
Additional equipment, built into the basic device:
Option Board “2 Binary Inputs” or B
2 external switches (supplied by SRD) release a control function in the
SRD, e.g. "close valve" (configurable)
Option Board “2 Binary Outputs” or
P
2 binary outputs (to be supplied externally) become active during value
limit in excess of the measured valve position
Option Board “2 Binary Inputs/Outputs” or
E
2 channels, each configurable as an input or output
(to be supplied externally)
Option Board “Position Feedback” F
1 output 4-20 mA (to be supplied externally) gives stroke / angle of rotation,
1 alarm output becomes active with a configurable event
Limit switch
T,U,
R,V
Supplies NAMUR signals when exceeding or falling below of two limit
values. Inductive sensors, independent of the controller,
in normal or safety version or three-wire, or micro switches
D Entry for remote potentiometer of external potentiometer unit
Pressure sensors
2 sensors measure the pressure of supply air and output y1 for Premi
-
um Diagnostics; the values are passed on via communication
LCD Full text graphic LCD in 3 languages
Accessories like Manifolds and Boosters see page 24.