PSS EVE0105 E-(en) SRD991 11
SRD991 with communication PROFIBUS-PA and FOUNDATION Fieldbus H1
SRD991-xPxxxx or SRD991-xQxxxx
PROFIBUS-PA
Datatransfer............according to PROFIBUS- PA
profile class B based on EN
50170 and DIN 19245 part 4
GSDfile................theactualfilecanbedown-
loaded from our homepage
Configuration
Local / Display ...........seepage 6
Software ...............VALcare™-DTM
Hardware...............PC-orPCMCIA-interfaces
from Softing
I/A Series System ........FBM223incombination with
CP60
Other control systems .....AllProfibus-PA- compatible,
e.g. Siemens SIMATIC PDM
(Process Device Manager)
FOUNDATION Fieldbus H1
Datatransfer............FFSpecificationRev.1.4,
Link-Master (LAS)
Two revisions of Firmware can be selected for the
FOUNDATION Fieldbus devices in the model code of the
positioner. The selection of the Firmware revision is
depending of the DCS compatibility, the DD Files already
installed in the DCS and the installed base on your site.
Double check interoperability of following characteristics
with your DCS before ordering!
When selected Firmware FF16 in the model code :
Certified according to ......ITK4.6
FunctionBlocks........PID,AO,2xDI,1xDO
Transducer, Resource
When selected Firmware FF18 in the model code :
Certified according to ......ITK6.0.1
FunctionBlocks........PID,AO,4xDI,1xDO,IS,OS,
AI, MAI, Transducer,
Resource
Additional functionality ...FlatAddressing
DD files ................theactualfilecanbedown-
loaded from our homepage
Configuration
Local / Display ...........seepage 6
Software ...............VALcare™-DTM
or National Instruments
NI-FBUS configurator
Hardware...............FBUS-interfacesfrom
National Instruments
(AT-FBUS and
PCMCIA- FBUS)
I/A Series System ........FBM220orFBM221in
combination with CP60
Other control systems .....AllFOUNDATION Fieldbus
H1- compatible, e.g. SMAR, Fisher Rosemount Delta-V,
Honeywell, Yokogawa, ABB
1) Data of ”Intrinsically Safe” version
For both fieldbus devices
Input signal .............digital
Supply voltage ...........DC9to32V
1)
max. Supply voltage.......DC36V
Operatingcurrent.........10.5mA±0.5mA(basecurrent)
Currentamplitude ........±8mA
Faultcurrent.............basecurrent+0mA
(base current + 4 mA by means of independent
FDE-safety circuit) according to IEC 1158-2
Operatingvalues.........accordingtoIEC1158-2
Start-up time (init phase) . . . approx. 2 sec
Bus connection ..........Fieldbus interface based on
IEC 1158-2 according to FISCO-Model
Power supply ............Power supply is achieved
dependant on the application by means of fieldbus
power supply units or segment coupler
Electrical classification thereto
seePage9