Directed Electronics VS102 Especificações Página 55

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 88
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 54
© Systeme Lauer GmbH & Co KG • Kelterstr.59 • 72669 Unterensingen • Tel. (07022) 96 60-0 • Fax (07022) 96 60-103
B-11
B Buep 19-Expander driver
The tasks are listed below in detail:
TASK PRIOR. LENGTH START CRITERION
1. Write keyboard status 8 3 When pressing or releasing a key
2. Reset message bit 7 2 Press CLR for delete behavior 2
3. Write PLC setpiont 6 2..3 Always after changing a setpoint variable
and leaving the entry field
4. Read actual values 5 2..24*) In priorities 0..6, 12 continuously, other-
wise when display is refreshed
5. Read message bits 4 9 max. Continuously
6. Send PCS status 4 5 After changes
7. Read LEDs, flashing 3 4 Continuously
LEDs, memory and
display behavior
8. Read command word 3 3 Continuously (menu selections only if the
temporary buffer is empty)
*) Depends on the number of variables displayed and if the addresses
are adjacent. If the addresses are not adjacent, one header is required
per non-adjacent variable (1 word).
Data transfer procedure When communicating with each other the PCS operates as master (AST).
It is the master´s task to set up the communication and to send orders to
the PLC. PCS and PLC communicate with the following settings: TTY or
RS-232C, 19200/9600/4800/1200 baud, 8 bit, EVEN parity, 1 stop bit.
Only the interchange of the packets is described in this manual. Refer to
the BOSCH „BUEP 19 transfer protocol“ manual for the structuring of the
packets.
Vista de página 54
1 2 ... 50 51 52 53 54 55 56 57 58 59 60 ... 87 88

Comentários a estes Manuais

Sem comentários